Search our site

Enter a keyword on the right to search our site.

PL511
10 port LCM

The PL500 range of 8 input/10 output, pluggable lighting control modules, providing solutions for switched, analogue and digital control.


Specifications

Features
10 circuit lighting control module
1-10V analogue dimming control (PL521)
Digital control (DALI - PL531, DSI - PL541)
LonWorks™ Interoperable solution
Simple integration and wiring
Extra low depth for shallow ceiling voids

Outputs
10 x independently addressable outputs
Emergency light test instigation

Inputs
8 x low voltage inputs for switch, occupancy, light level and infra-red and emergency light test monitoring sensors
1 x scene setting input

Networking
LonWorks™ network TP/FT-10 (Capacitordecoupled)
DALI on output port pins 5 and 6(PL531)
DSI on output port pins 5 and 6(PL541)
1-10v on output port pins 5 and 6(PL521)

Cabling and Connectors
Mains input
LonWorks™ interface
Sensor connectors
10 x outputs - WielandGST18i6

Dimensions
250mm x 250mm x 47.5mm (LxWxH)

Fixings
2 x 9mm fixing holes (suitable for drop rod and surface mounting)
4 x 7mm holes for drop rod or surface mounting

Safety
BS EN 62368
Isolation: 4kV between mains and
sensors/network/digital control

Conformity and Standards
Generic emission: EN 6100
Generic immunity: EN 6100
LonMark™ compliant DALI and DSI compliant
ARCOM MasterSpec 2013 Classification 29 0933

Environment
Storage
Temperature: -10˚c - +60˚c
Humidity: 0% - 90% non condensing

InUse
Temperature: 0˚c -+40˚c
Humidity: 10% - 90% non condensing

MainsInput
Mains supply: 230Vac +/- 10%;50Hz
Connections: input male socket for PC013 Wieland GST18i3 female plug Plug not included (Available fromProlojik)
Combined power and network via EST2i3 FSK plug Plug not included (Available from Prolojik)
Structured cabling connector Wieland Part:EST2i3FSK

Outputs
Connections: output female socket for PC016 WielandGST18i6 male plug
Plugs not included (Available from Prolojik)
Switching capability: 1000VA per output maximum
Maximum total load: 16A total peak load - refer to Prolojik for load types
Emergency maintained capacity: 1000VA total maximum
Analogue dimming: 1-10Vdc at 5mA per output current sinking (PL521)
Digital dimming: 250mA maximum 15Vdc(PL531/PL541)
Suggested load max 4 x ballasts per output

Sensor & Switch inputs
Sensor supply: 12Vdc +/- 5%,30mA Sensor isolation:2kV