Search our site

Enter a keyword on the right to search our site.

PS320
DALI External Photocell

The external photocell connects to Prolojik LCMs and hubs to provide a sample of external daylight levels for use with daylight linking.

An Integral feedback LED allows for the installer to easily verify correct wiring and identify connection.

Prolojik’s PS320 External Photocell is designed to work with Prolojik PL and PC series lighting controllers. The photocell delivers high accuracy light level measurement.


Specifications

Performance
Light Level
Sensor type: Photo-diode Accuracy: +/-5% across range Field of view: 360˚

Environment
Storage
Temperature: -40˚C to +80˚C
Humidity: 0% - 90% non-condensing

In Use
Temperature: -40 to +80˚C
Humidity: 10% - 90% non-condensing

Conformity & Standards
EMC immunity EN 6100 EMC emissions EN 6100
Housing material flame-proof ABS DALI & NEMA compliant
IEC Standard 62386-102 NEMA Standard NS243-2004
Supports DALI 2 & 3 byte protocol
ARCOM MasterSpec 2013 Classification 29 09 23
 
Enclosure
Transparent Poly-carbonate Lid ABS IP65 Enclosure

Dimensions
80mm x 82mm x 55mm (L x W x H) Weight 40g

Commissioning aids
IR reception from PC101 - triple flash Reboot - Rapid Flash

Installation
Photocell should be mounted north facing
Do NOT mount photocell sensor in an obscured location

Photocell Connector
PC032 2 pole screw terminal connector (for DA, DA connections) via 20mm gland
Plug included
Cable diameters 0.5 to 2.5mm2
CE and UL approved