PL910CBS Relay Control Unit

PL910 - CBS Relay Control Unit

Features

IP66 Steel Wall Box.
Pre-drilled for mounting and cable entries (5 x 20mmØ).
Ceramic Terminals for Batt connection.
IK10 Impact Strength.
Automatic supply switching.
DALI monitoring of relay status.
<500ms switch over relay.

The Prolojik PL910 is an enclosure housing the PL110 central battery relay control unit, monitoring a mains power line and switching over to a dedicated supply when the normal supply is broken. The PL110 also provides monitoring on the status of the supply to the DALI channel.

Specifications

Connections

Mains input: L, E, N Push Terminal connections.
Battery Supply input: L, E, N Screw Ceramic Terminal connections.
Mains Output: L, E, N Screw Terminal connections.
DALI Bus: 3 x push terminal connections.

Internal Wiring

Mains / Battery:2.5mm2 TRI RATED.
DALI:1.5mm2 TRI RATED.

Dimensions

200 mm x 200 mm x 120 mm (LxWxH).

Safety

EN 62368-1.
Isolation: 4kV between mains & outputs.

Relay Switch over

<500ms switch over time.

Conformity & Standards

Generic emission: EN 61000-6-3.
Generic immunity: EN 61000-6-1.
LonMarkTM compliant.
DALI compliant.
Supports DALI 2 & 3 byte protocol.

Environment

Storage
Storage Temperature: -10°c -+60°c.
Humidity: 0 % -90 % non condensing.
In Use
Temperature: 0°c -+40°c.
Humidity: 10% -90% non condensing.
IP66 enclosure.

Mains Supply

230 –400V Ac, 47-63 Hz.
5A unswitched fused spur (1A minimum).

Power Consumption

4mA nominal consumption at 15V DALI bus voltage.

Technical Data

Diagram 1 - PL910 - CBS Relay Control Unit

 

Features

IP66 Steel Wall Box.
Pre-drilled for mounting and cable entries (5 x 20mmØ).
Ceramic Terminals for Batt connection.
IK10 Impact Strength.
Automatic supply switching.
DALI monitoring of relay status.
<500ms switch over relay.